Set Model |
AUC-48TR6RNKA |
Indoor Model |
AUC-48TR4RKA |
Outdoor Model |
AUW-48T6RN |
Panel Model |
PE-QFA/B |
Remote Controller Model |
L1-12 |
Power Supply (Indoor) |
220/1/50 V/Ph/Hz |
Power Supply (Outdoor) |
380/3/50 V/Ph/Hz |
Max. Input Consumption |
6600 W |
Max. Input Current |
12 A |
Cooling Capacity |
48000 Btu/h / 14000 W |
Cooling Capacity Range |
4400-16000 W |
Input Power |
4900 W |
Input Power Range |
1000-6300 W |
Current |
8.6 A |
EER |
2.86 W/W |
SEER |
14.00 |
Cooling Capacity (Test Data Pingdu) |
14418 W |
Input Power (Test Data Pingdu) |
4711 W |
EER (Test Data Pingdu) |
3.06 W/W |
Indoor Fan Motor Model |
SIC-76FX-F1101-1 |
Indoor Fan Motor Quantity |
1 |
Indoor Fan Motor Output |
101 W |
Indoor Fan Motor Speed (Hi/Med/Lo) |
720/640/570 r/min |
Indoor Coil Number of Rows |
3 |
Indoor Coil Tube Pitch (a) x Row Pitch (b) |
21×13.6 mm |
Fin Spacing |
1.5 mm |
Fin Type |
Hydrophilic aluminium |
Tube Outside Diameter and Type |
Ф7, innergroove tube |
Coil Dimensions (LxHxW) |
2096×231×40.8 mm |
Number of Circuits |
5 |
Indoor Air Flow Rated (Hi/Med/Lo) |
2000/1750/1550 m³/h |
Indoor Air Flow Rated (Hi/Med/Lo) |
1170/1030/910 CFM |
Indoor Noise Level Rated (Sound Pressure) |
52/50/48 dB(A) |
Indoor Unit Dimension (WxHxD) |
840×272×840 mm |
Indoor Unit Packing (LxHxW) |
950×950×360 mm |
Indoor Unit Net/Gross Weight |
26/32 kg |
Panel Dimension (WxHxD) |
950×50×950 mm |
Panel Packing (LxHxW) |
1020×1000×105 mm |
Panel Net/Gross Weight |
6.5/9 kg |
Drainage Water Pipe Diameter |
ODΦ32 mm |
Operation Temperature |
16~30 ℃ |
Qty per 20’ / 40’ / 40’HQ (Indoor Unit) |
72/144/168 Set |
Compressor Model |
KTF400D64UMT |
Compressor Type |
Twin ROTARY |
Compressor Brand |
GMCC |
Compressor Capacity |
44360 Btu/h |
Compressor Input |
3155 W |
Rated Current (RLA) |
13 A |
Refrigerant Oil |
POE VG74 1000ML |
Outdoor Fan Motor Model |
ZW511A800002 |
Outdoor Fan Motor Quantity |
2 |
Outdoor Fan Motor Output |
60 W |
Outdoor Fan Motor Speed (Hi) |
880 r/min |
Outdoor Coil Number of Rows |
2 |
Outdoor Coil Tube Pitch (a) x Row Pitch (b) |
21×21.65 mm |
Outdoor Coil Fin Spacing |
1.5 mm |
Outdoor Coil Fin Type |
Hydrophilic aluminium |
Outdoor Coil Tube Outside Diameter and Type |
Ф7.94, innergroove tube |
Outdoor Coil Dimensions (LxHxW) |
894×1134×43 mm |
Outdoor Coil Number of Circuits |
6 |
Outdoor Noise Level Rated (Sound Pressure) |
56 dB(A) |
Throttle Type |
EEV |
Outdoor Unit Dimension (WxHxD) |
900×1170×320 mm |
Outdoor Unit Packing (WxHxD) |
970×1300×430 mm |
Outdoor Unit Net/Gross Weight |
105/115 kg |
Refrigerant Type/Quantity |
R32, Charged volume 2.47 kg |
Design Pressure |
4.3/1.6 MPa |
Refrigerant Piping (Liquid/Gas side) |
Φ9.52/Φ15.88 (3/8″/5/8″) |
Max. Pipe Length |
50 m |
Max. Difference in Level |
30 m |
Ambient Temperature (Cooling) |
-7~48 ℃ |
Qty per 20’ / 40’ / 40’HQ (Outdoor Unit) |
31/63/126 Set |
Qty per 20’ / 40’ / 40’HQ (Other) |
26/58/66 Set |